Fault guide · heater and circuit
Water heater trips the RCCB — the fault is often not the heater
An RCCB trips on earth leakage. Inside a water heater there is water, a heating element and a switch, all of which can leak current to earth. Outside it there is an isolator, cable and a breaker — and any of those can produce exactly the same symptom.
Stop using the heater and switch its isolator off. If the RCCB trips only when the heater runs, the element or the heater's internal wiring is the usual suspect. If it trips with the heater switched off at the isolator, the fault is in the circuit or isolator. Either way it needs an insulation test, and if the heater is the cause, the heater work and the electrical check should be one coordinated visit.
Four faults, one symptom
| What is happening | Likely fault | Who fixes it |
|---|---|---|
| RCCB trips seconds after the heater starts | Element insulation failure — current leaking through water | Heater technician replaces the element; electrician confirms the circuit after |
| Trips when the heater switch is turned on, before heating | Moisture in the isolator or switch, or a damaged cable to the heater | Licensed electrician replaces the isolator or repairs the cable |
| Trips with the heater isolator off | Fault elsewhere on that circuit, not the heater | Licensed electrician tests the circuit and isolates the leaking section |
| Trips after rain or after a long shower | Moisture ingress at an outdoor point or through a cracked seal | Heater and enclosure inspection plus accessory replacement |
Green lights and red herrings
A heater can heat perfectly well and still leak current to earth — the element does not have to be dead to be unsafe. That is why 'it still gets hot' is not evidence the heater is fine, and why replacing the RCCB instead of testing the heater simply moves the trip to the next device.
Safe steps tonight
- Switch the heater isolator off. If there is no isolator, switch the circuit off at the DB.
- Do not reset the RCCB and immediately retry the heater to see what happens.
- If water is dripping near the heater or switch, keep the area dry and do not touch the fittings.
- If the heater serves a tenanted unit, tell the tenant what is isolated and why.
Why one coordinator matters here
The common outcome is a heater technician who says the heater is fine and an electrician who says the circuit is fine, with the customer paying twice and still having a trip. AOT runs plumbing and heater coordination alongside electrical work, so the heater, the isolator and the circuit are tested as one system. Where the cause is the element, the heater is repaired and the circuit re-tested; where it is the circuit, only the electrical work is charged.
What to send
- A photo of the heater, including the model label
- A photo of the isolator or switch, and the DB label for that circuit
- Whether it trips instantly, after a few minutes, or only after long use
- Whether there is any dripping, staining or corrosion around the unit
Questions owners and managers ask
Can I still use the shower if the heater trips?
No. An RCCB trip on a heater circuit indicates leakage to earth, and water is the path. Keep the heater isolated until the cause is found, even if the water is still warm.
Why does it only trip sometimes?
Intermittent leakage usually tracks moisture: a seal that weeps, a switch that holds damp, or an element that leaks more as it heats. Intermittent does not mean safe, and it usually gets more frequent.
Is it the heater or the wiring?
That is what the insulation test answers. Testing the heater in isolation and then the circuit separately tells you which side the leakage is on, and stops you paying for the wrong repair.
Do I need to replace the whole heater?
Usually not. Elements, thermostats and isolators are serviceable parts. Replacement becomes the answer when the tank or body is corroded or cracked.
Does AOT do the heater work and the electrical work?
AOT coordinates both, including its own plumbing and heater capability. The electrical installation work is carried out by an EMA-licensed consortium partner within licence scope, and the result is one scope and one visit window rather than two contractors.
Need this looked at properly?
Send three photos and the pattern. We confirm scope, who attends and a price band before anyone travels. Mon–Sat 08:00–17:00.