Why does my DB box keep tripping?
A tripping DB box in a Singapore flat is usually earth leakage, not a worn breaker: the 30 mA RCCB trips when current escapes through water, a failing heater element or damaged insulation. Isolate the circuit, stop resetting it, and have the leakage traced with an insulation test. From S$60 after a photo.
Updated 30 Oct 2026 · AOT Electrical, a trade site of ALPHA & OMEGA TRINITY PTE. LTD. (UEN 201215586K)
One trip or many? Read the board before touching a breaker
There are two different devices in a Singapore consumer unit and they report two different faults. Mixing them up is why people replace a good breaker and the tripping continues.
| What you see | Likely cause | What we check |
|---|---|---|
| The main RCCB (with the test button) trips and takes the whole flat down | Earth leakage — current escaping through water, a failing element or damaged insulation | Insulation resistance on each circuit with the appliances unplugged, then reconnected one at a time |
| Only one MCB trips; the rest of the flat stays on | Overload or short circuit on that one circuit | Load on the circuit with a clamp meter, then the wiring and every accessory on that run |
| Trips seconds after the storage heater or aircon starts | Element sheath failure, or moisture in an outdoor isolator or compressor terminal | The appliance isolated and megger-tested cold, then watched as it heats and draws |
| Trips at random, worse after rain | Water in an outdoor point, a wet light fitting, or a corroded joint in a service yard | Every external point and its enclosure; the outdoor unit isolator is usually first |
| Trips when you plug in one particular appliance | That appliance, not the house wiring | The appliance's own insulation and plug; if it passes, the socket it uses |
| Breaker feels hot, smells of scorching, or buzzes | Loose terminal or an undersized/ageing device — a fire risk, not a reset problem | Terminal torque and heat on the board itself; the supply is left off until this is resolved |
What happens when you engage AOT
- Send a photo. The board with the tripped switch visible, plus one photo of the appliance that seems to set it off. We reply with the likely fault and a from-price of S$60 for diagnosis.
- Survey on site. We confirm which device tripped, isolate circuits, and test insulation and load — no parts swapped on a guess.
- Written quote. You get the fault, the fix and the price in writing before work starts. Diagnosis is applied against the repair if you proceed.
- Repair and retest. The faulty circuit or device is repaired or replaced, then each circuit is re-energised and tested one at a time.
Hours are Monday to Saturday, 08:00–17:00, closed Sunday and public holidays. Regulated electrical work is carried out or supervised by an EMA Licensed Electrical Worker through our licensed consortium partners; no personal LEW number is published here.
Questions we get asked on WhatsApp
- Why does my DB box trip only when the heater or aircon starts?
- A load that trips the supply the moment it starts is usually leaking to earth, not drawing too much power. A storage heater element with a pinhole in its sheath, or a wet aircon outdoor isolator, shows near-zero leakage cold and faults as it heats up. That is why the breaker holds for minutes and then trips.
- Is it safe to keep resetting the breaker?
- No. A breaker that trips is reporting a fault it has already detected. Resetting repeatedly, or taping it up, lets the fault keep running — that is how scorched terminals and DB fires start. Switch the circuit off at the DB and leave it off until it is tested.
- How much does it cost to find the fault?
- AOT diagnoses from S$60 after a photo of the DB, applied against the repair if you proceed. A board with several suspect circuits, or one that needs a full insulation test on every circuit, is quoted after the survey. No price is invented before the board is seen.
- Can you tell from a photo which circuit is tripping?
- A photo usually tells us which device tripped — main RCCB, one MCB, or an RCBO — and that narrows the fault to a whole-house leakage or a single circuit. It cannot measure leakage, so the insulation and clamp tests still happen on site.
- Do I need a Licensed Electrical Worker for this work?
- Yes. Regulated electrical work in Singapore must be carried out or supervised by an EMA Licensed Electrical Worker. AOT works with EMA-licensed consortium partners and does not publish a personal LEW number on this site.