A tripping DB box in a Singapore flat is usually earth leakage, not a worn breaker: the 30 mA RCCB trips when current escapes through water, a failing heater element or damaged insulation. Isolate the circuit, stop resetting it, and have the leakage traced with an insulation test. From S$60 after a photo.

Updated 30 Oct 2026 · AOT Electrical, a trade site of ALPHA & OMEGA TRINITY PTE. LTD. (UEN 201215586K)

One trip or many? Read the board before touching a breaker

There are two different devices in a Singapore consumer unit and they report two different faults. Mixing them up is why people replace a good breaker and the tripping continues.

Symptom → likely cause → what a competent electrician checks
What you seeLikely causeWhat we check
The main RCCB (with the test button) trips and takes the whole flat downEarth leakage — current escaping through water, a failing element or damaged insulationInsulation resistance on each circuit with the appliances unplugged, then reconnected one at a time
Only one MCB trips; the rest of the flat stays onOverload or short circuit on that one circuitLoad on the circuit with a clamp meter, then the wiring and every accessory on that run
Trips seconds after the storage heater or aircon startsElement sheath failure, or moisture in an outdoor isolator or compressor terminalThe appliance isolated and megger-tested cold, then watched as it heats and draws
Trips at random, worse after rainWater in an outdoor point, a wet light fitting, or a corroded joint in a service yardEvery external point and its enclosure; the outdoor unit isolator is usually first
Trips when you plug in one particular applianceThat appliance, not the house wiringThe appliance's own insulation and plug; if it passes, the socket it uses
Breaker feels hot, smells of scorching, or buzzesLoose terminal or an undersized/ageing device — a fire risk, not a reset problemTerminal torque and heat on the board itself; the supply is left off until this is resolved
Do this before anything else: switch the affected circuit off at the DB, unplug what you can, and leave the board alone. Do not reset a breaker that keeps tripping, and never tape or wedge it closed.

What happens when you engage AOT

  1. Send a photo. The board with the tripped switch visible, plus one photo of the appliance that seems to set it off. We reply with the likely fault and a from-price of S$60 for diagnosis.
  2. Survey on site. We confirm which device tripped, isolate circuits, and test insulation and load — no parts swapped on a guess.
  3. Written quote. You get the fault, the fix and the price in writing before work starts. Diagnosis is applied against the repair if you proceed.
  4. Repair and retest. The faulty circuit or device is repaired or replaced, then each circuit is re-energised and tested one at a time.

Hours are Monday to Saturday, 08:00–17:00, closed Sunday and public holidays. Regulated electrical work is carried out or supervised by an EMA Licensed Electrical Worker through our licensed consortium partners; no personal LEW number is published here.

Questions we get asked on WhatsApp

Why does my DB box trip only when the heater or aircon starts?
A load that trips the supply the moment it starts is usually leaking to earth, not drawing too much power. A storage heater element with a pinhole in its sheath, or a wet aircon outdoor isolator, shows near-zero leakage cold and faults as it heats up. That is why the breaker holds for minutes and then trips.
Is it safe to keep resetting the breaker?
No. A breaker that trips is reporting a fault it has already detected. Resetting repeatedly, or taping it up, lets the fault keep running — that is how scorched terminals and DB fires start. Switch the circuit off at the DB and leave it off until it is tested.
How much does it cost to find the fault?
AOT diagnoses from S$60 after a photo of the DB, applied against the repair if you proceed. A board with several suspect circuits, or one that needs a full insulation test on every circuit, is quoted after the survey. No price is invented before the board is seen.
Can you tell from a photo which circuit is tripping?
A photo usually tells us which device tripped — main RCCB, one MCB, or an RCBO — and that narrows the fault to a whole-house leakage or a single circuit. It cannot measure leakage, so the insulation and clamp tests still happen on site.
Do I need a Licensed Electrical Worker for this work?
Yes. Regulated electrical work in Singapore must be carried out or supervised by an EMA Licensed Electrical Worker. AOT works with EMA-licensed consortium partners and does not publish a personal LEW number on this site.